2014-10-22

apc oid for monitoring bypass input voltage

Usually, input2  is for Bypass .
 
Each input has 3 phases.
  
the result from a UPS without bypass
check_snmp -H  APC_HOST1  -C public -o .1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.2.1.1
SNMP OK - 0 | PowerNet-MIB::upsPhaseInputVoltage.2.1.1=0
 
the result from a UPS with bypass
check_snmp -H APC_HOST2  -C public -o .1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.2.1.1
SNMP OK - 230 | PowerNet-MIB::upsPhaseInputVoltage.2.1.1=230

2.1.1 ( at the end of the OID) means :
2   input 2(bypass) ,
1   unknown
1    phase1
 
 
 